The In-suite Isolator model FW859is designed to allow Maple Armor’s intelligent addressable fire control panels to be used in high density residential and hospitality applications. With this module installed, wire-to-wire fault on one NAC circuit will not have an effect on any other circuit or device in the system.The In-suite Isolator is capable of detecting a short circuit condition on the field wiring side, and isolating the field wiring once this condition is detected by causing an open circuit condition to occur.
The FW859 provides two supervised isolator outputs. Under this configuration, if the in-suite audible device has an open circuit, the fire control panel will indicate a zone trouble.
SPECIFICATION
|
Operating Voltage |
Regulated 16 - 33VDC/FWR |
|
Standby Current |
0.1 mA |
|
Active Current |
34 mA |
|
Maximum Switching Current |
10 A |
|
Minimum Switching Current |
400 mA |
|
Wire Size |
12 to 18AWG |
|
Operating Temperature |
0° to 49°C (32° to 120°F) |
|
Operating Humidity |
0 to93% RH |
|
Location |
Indoor use only |
INSTALLATION
1. Mount the base onto a 4x4 electrical box or combine the Printed Circuit Board (PCB) fixed structure and backbox model FW800using the screws provided, see Figure 1.
Figure 1 Module Installation
2. Connect the wirings. See Figure 2 and Figure 3.
(a) Class A
(b) Class B
Figure 2 NAC wiring
Figure 3 Field Wiring
MAINTENANCE
Scheduled inspection and operational test should be carried as per requirement set out by Local Authority Having Jurisdiction.
Return the module for repair if it fails in operation. Do not disassemble the module without permission.